Floor convector with fan HCX 4P

VERY EFFICIENT DOUBLE-CIRCUIT TRENCH HEATER
WITH A FAN FOR HEATING AND COOLING

CHARACTERISTIC

• body made from high quality stainless steel
• high forced convection output
• rapid room heating
• heating also when the fan is off
• contains own microprocessor-controlled unit
• designed also for cooling
• safe 24 V DC voltage
• low electricity consumption
• also suitable for heat pump

Updated 2/2019

DIMENSIONS

  • Width 340 mm
  • Build height 195 mm
  • Length 900 - 3000 mm

INDIVIDUAL HEATING OUTPUT CALCULATION

mm
mm
(900 - 3000 mm)
°C
°C
Mean water temperature: - °C
°C
Heating output: - W
It is necessary to increase the mean or outlet water temperature for the proper function of thermocouples.
The outlet water temperature must be higher than the air temperasture.

INDIVIDUAL COOLING OUTPUT CALCULATION

mm
mm
(900 - 3000 mm)
°C
°C
Mean water temperature: - °C
°C
Cooling output: - W
COIL HCX 4P - heating 900 1000 1250 1500 1750 2000 2250 2500 2750 3000 length (mm)
0th fan speed; 141 165 223 282 341 400 458 517 576 635 heat power (W)
1st fan speed; 1293 1509 2047 2586 3125 3664 4202 4741 5280 5819 heat power (W)
2nd fan speed; 2472 2884 3914 4944 5974 7004 8034 9064 10094 11124 heat power (W)
3rd fan speed; 3397 3963 5379 6794 8209 9625 11040 12456 13871 15287 heat power (W)
COIL HCX 4P - cooling (sensitive) 900 1000 1250 1500 1750 2000 2250 2500 2750 3000 length (mm)
2nd fan speed; 559 652 884 1117 1350 1583 1815 2048 2281 2514 cool power (W)
3rd fan speed; 815 950 1290 1629 1969 2308 2648 2987 3326 3666 cool power (W)
COIL HCX 4P - DC MOTOR 900 1000 1250 1500 1750 2000 2250 2500 2750 3000 length (mm)
  17 18 50 75 84 90 93 102 150 168 power input (VA)