Floor convector with fan HC

Very efficient single circuit floor convector with a fan for heating and cooling. Suitable for all types of interiors. This convector is standardly supplied with a DC fan motor or, for use in a wet environment, with an AC motor.

CHARACTERISTIC

  • single circuit connection
  • high forced convection heating efficiency
  • rapidly reacting heating unit
  • heats even when the fan is turned off
  • simple control
  • designet also for cooling

    Updated 2/2019

DIMENSIONS

  • Width 243 mm
  • Build height 125 mm
  • Length 900 - 3000 mm

INDIVIDUAL HEATING OUTPUT CALCULATION

mm
mm
(550 - 3000 mm)
°C
°C
Mean water temperature: - °C
°C
Heating output: - W
It is necessary to increase the mean or outlet water temperature for the proper function of thermocouples.
The outlet water temperature must be higher than the air temperasture.

INDIVIDUAL COOLING OUTPUT CALCULATION

mm
mm
(550 - 3000 mm)
°C
°C
Mean water temperature: - °C
°C
Cooling output: - W
COIL HC - heating 900 1000 1250 1500 1750 2000 2250 2500 2750 3000 length (mm)
1st fan speed; 869 1013 1375 1737 2099 2461 2823 3185 3546 3908 heat power (W)
2nd fan speed; 1101 1285 1743 2202 2661 3120 3578 4037 4496 4955 heat power (W)
3rd fan speed; 1318 1538 2087 2636 3185 3734 4284 4833 5382 5931 heat power (W)
COIL HC - cooling (sensitive) 900 1000 1250 1500 1750 2000 2250 2500 2750 3000 length (mm)
2nd fan speed; 328 383 519 656 792 929 1066 1202 1339 1476 cool power (W)
3rd fan speed; 438 511 694 877 1060 1242 1425 1608 1790 1973 cool power (W)
COIL HC - DC MOTOR 900 1000 1250 1500 1750 2000 2250 2500 2750 3000 length (mm)
  15 20 26 37 40 46 53 64 75 77 power input (VA)
COIL HC - AC MOTOR 900 1000 1250 1500 1750 2000 2250 2500 2750 3000 length (mm)
  51 61 61 102 122 122 153 173 183 183 power input (VA)

The technical parameters are set according to the relevant standards. In fact, they may vary depending on the location of the convector, the cover grille, the connection type.

Language select