Floor convector with fan HC4p

Very effi cient two-circuit floor convector with a fan for heating and cooling. The two-circuit connection permits use of the cooling and heating circuits separately. Consequently, it is suitable for all types of interiors. 

CHARACTERISTIC

  • double circuit connection
  • high forced convection output
  • rapidly reacting heating/cooling output
  • heats even when the fan is turned off
  • simple control
  • designed also for cooling

    Updated 2/2019

DIMENSIONS

  • Width 303 mm
  • Build height 132 mm
  • Length 900 - 3000 mm

INDIVIDUAL HEATING OUTPUT CALCULATION

mm
mm
(550 - 3000 mm)
°C
°C
Mean water temperature: - °C
°C
Heating output: - W
It is necessary to increase the mean or outlet water temperature for the proper function of thermocouples.
The outlet water temperature must be higher than the air temperasture.

INDIVIDUAL COOLING OUTPUT CALCULATION

mm
mm
(550 - 3000 mm)
°C
°C
Mean water temperature: - °C
°C
Cooling output: - W
COIL HC4p - heating 900 1000 1250 1500 1750 2000 2250 2500 2750 3000 length (mm)
1st fan speed; 634 740 1004 1268 1532 1796 2061 2325 2589 2853 heat power (W)
2nd fan speed; 861 1004 1362 1721 2080 2438 2797 3155 3514 3872 heat power (W)
3rd fan speed; 1033 1205 1635 2065 2495 2925 3356 3786 4216 4646 heat power (W)
COIL HC4p - cooling (sensitive) 900 1000 1250 1500 1750 2000 2250 2500 2750 3000 length (mm)
2nd fan speed; 261 305 414 523 632 741 850 958 1067 1176 cool power (W)
3rd fan speed; 357 417 566 715 864 1013 1162 1311 1460 1609 cool power (W)
COIL HC4p - DC MOTOR 900 1000 1250 1500 1750 2000 2250 2500 2750 3000 length (mm)
  15 20 26 37 40 46 53 64 75 77 power input (VA)

The technical parameters are set according to the relevant standards. In fact, they may vary depending on the location of the convector, the cover grille, the connection type.

Language select