Floor convector with fan HCM4p

Most efficient floor convector of the MINIB range with two-circuit separated system for the heating and cooling circuit. The two-circuit connection permits use of the heating and cooling circuits separately.

CHARACTERISTIC

  • two-circuit connection
  • rapidly reacting heating unit
  • heats even when the fan is turned off
  • very high forced convection heating efficiency
  • safe 12 V DC voltage
  • simple control
  • designed also for cooling

    Updated 2/2019

DIMENSIONS

  • Width 340 mm
  • Build height 147 mm
  • Length 900 - 3000 mm

INDIVIDUAL HEATING OUTPUT CALCULATION

mm
mm
(550 - 3000 mm)
°C
°C
Mean water temperature: - °C
°C
Heating output: - W
It is necessary to increase the mean or outlet water temperature for the proper function of thermocouples.
The outlet water temperature must be higher than the air temperasture.

INDIVIDUAL COOLING OUTPUT CALCULATION

mm
mm
(550 - 3000 mm)
°C
°C
Mean water temperature: - °C
°C
Cooling output: - W
COIL HCM4p - heating 900 1000 1250 1500 1750 2000 2250 2500 2750 3000 length (mm)
1st fan speed; 923 1077 1462 1846 2231 2616 3000 3385 3770 4154 heat power (W)
2nd fan speed; 1037 1210 1642 2074 2506 2939 3371 3803 4235 4667 heat power (W)
3rd fan speed; 1170 1365 1853 2340 2828 3315 3803 4290 4778 5265 heat power (W)
COIL HCM4p - cooling (sensitive) 900 1000 1250 1500 1750 2000 2250 2500 2750 3000 length (mm)
2nd fan speed; 524 612 830 1049 1267 1486 1704 1923 2141 2360 cool power (W)
3rd fan speed; 736 859 1166 1473 1780 2087 2393 2700 3007 3314 cool power (W)
COIL HCM4p - DC MOTOR 900 1000 1250 1500 1750 2000 2250 2500 2750 3000 length (mm)
  22 22 40 44 56 69 80 85 89 109 power input (VA)

The technical parameters are set according to the relevant standards. In fact, they may vary depending on the location of the convector, the cover grille, the connection type.